The aim of the study was to measure occupational exposure to electric and magnetic fields during various work tasks at switching and transforming stations of 110 kV (in some situations 20 kV), and analyze if the action values of European Union Directive 2004/40/EC or reference values of International Commission on Non-ionizing Radiation Protection (ICNIRP) were exceeded. The electric (n = 765) and magnetic (n = 203) fields were measured during various work tasks. The average values of all measurements were 3.6 kV m(-1) and 28.6 muT. The maximum value of electric fields was 15.5 kV m(-1) at task 'maintenance of operating device of circuit breaker from service platform'. In one special work task close to shunt reactor cables (20 kV), the highest magnetic field was 710 muT. In general, the measured magnetic fields were below the reference values of ICNIRP.
机译:该研究的目的是测量110 kV(在某些情况下为20 kV)转换和变电站的各种工作任务期间在电场和磁场中的职业暴露,并分析欧盟指令2004/40 / EC的作用值是否或超过了国际非电离辐射防护委员会(ICNIRP)的参考值。在各种工作任务中测量了电场(n = 765)和磁场(n = 203)。所有测量的平均值为3.6 kV m(-1)和28.6 muT。在“从服务平台维修断路器的操作装置”任务中,电场的最大值为15.5 kV m(-1)。在靠近并联电抗器电缆(20 kV)的一项特殊工作中,最高磁场为710 muT。通常,测得的磁场低于ICNIRP的参考值。