首页> 外文期刊>The Journal of Infectious Diseases >A community-wide outbreak of legionnaires disease linked to industrial cooling towers--how far can contaminated aerosols spread?
【24h】

A community-wide outbreak of legionnaires disease linked to industrial cooling towers--how far can contaminated aerosols spread?

机译:与工业冷却塔相关的社区范围内的军团菌疾病暴发-受污染的气溶胶可以传播到多远?

获取原文
获取原文并翻译 | 示例
       

摘要

A community-wide outbreak of legionnaires disease occurred in Pas-de-Calais, France, in November 2003-January 2004. Eighteen (21%) of 86 laboratory-confirmed cases were fatal. A case-control study identified smoking, silicosis, and spending >100 min outdoors daily as risk factors for acquiring the disease. Legionella pneumophila strain Lens was isolated from cooling towers, wastewater, and air samples from plant A. This unique strain matched all 23 clinical isolates, as assessed by pulsed-field gel electrophoresis subtyping. Modeling of atmospheric dispersion of aerosols emitted from plant A cooling towers showed good coverage of the communes where patients lived and showed that the dispersion extended over a distance of at least 6 km from plant A. No other aerosol-producing installation was identified as a plausible source, and no common source of indoor exposure was found. These findings implicate plant A as the most likely outbreak source and suggest that the distance of airborne transmission of L. pneumophila may be greater than previously reported.
机译:2003年11月至2004年1月在法国的加来海峡爆发了军团菌病的全社区爆发。在86例实验室确认的病例中,有18例(21%)是致命的。一项病例对照研究确定吸烟,矽肺和每天在户外花费100分钟以上是感染该疾病的危险因素。军团菌嗜肺军团菌从工厂A的冷却塔,废水和空气样本中分离出Lens。这种独特的菌株与所有23种临床分离株相匹配,通过脉冲场凝胶电泳亚型评估。从工厂A冷却塔排放的气溶胶在大气中的扩散模型表明,患者居住的社区覆盖良好,并且表明该扩散距离工厂A至少延伸了6 km。没有发现其他可能的气溶胶产生装置来源,没有发现室内暴露的常见来源。这些发现暗示植物A是最可能的暴发源,并表明肺炎链球菌的空气传播传播距离可能比以前报道的要大。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号