首页> 外文期刊>PowerPlant Chemistry: The Journal of All Power Plant Chemistry Areas >Loss of Alkalization in an Alkaline Treated Stator Cooling Water System
【24h】

Loss of Alkalization in an Alkaline Treated Stator Cooling Water System

机译:碱性处理的定子冷却水系统中的碱化损失

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Alkaline treatment of stator cooling water (SCW) systems with copper hollow conductors performs best when pH and dissolved oxygen are kept constant. In the event of loss of alkalization, pH will return to neutral and this will destabilize existing copper oxide layers. Operating experience, however, indicates that infrequent and short-term loss of alkalization does not result in a detrimental buildup of copper oxides in the stator hollow conductors. Thus there is the question as to how long and how often a loss of alkalization can be tolerated. Although operating experience suggests that loss of alkalization can be tolerated for short periods, it is not recommended to allow this routinely and, to the extent practical, SCW pH should be kept constant. Although there is no hard data to support this, an international expert consensus has been found that loss of alkalization of up to one week, and not more than two occurrences per year, can be tolerated. Upon loss, alkalization should be restored to normal as soon as possible. If the loss of alkalization is longer, it is recommended to monitor the water pressure drop across the coils and, if available, also the stator bar temperatures.
机译:当pH和溶解氧保持恒定时,用铜空心导体对定子冷却水(SCW)系统进行碱性处理效果最佳。如果失去碱化作用,pH值将恢复为中性,这将破坏现有氧化铜层的稳定性。然而,操作经验表明,很少和短期的碱化损失不会导致定子空心导体中氧化铜的有害堆积。因此存在一个问题,即碱化的损失可以容忍多长时间和多久可以容忍一次。尽管操作经验表明碱化的损失可以在短时间内忍受,但不建议常规进行,并且在实际操作中应将SCW pH保持恒定。尽管没有确凿的数据可以证明这一点,但国际专家一致认为,可以忍受长达一周的碱化损失,每年最多可以忍受两次碱化。丢失后,碱化应尽快恢复正常。如果碱化损失时间较长,建议监测线圈两端的水压降,如果有的话,还要监测定子棒的温度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号