In power system load flow studies, it is common to ignore wind park (WP) losses completely, since WPs are obliged to provide reactive power as a free-of-charge ancillary service. Strongly simplified WP loss estimations are also widespread. Prevailing loss modelling approaches may result in substantial and so far usually ignored reactive power allocation inefficiencies. The innovation of this paper lies in demonstrating this and in presenting an alternative modelling approach that combines speed, ease-of-use and accuracy. Calculations are based on a generic WP connected to 110kV. It is simulated once using gearless permanent magnet synchronous generators and once using doubly fed induction generators. In this way, for the first time, the consequences of neglecting differences between wind generator types when calculating reactive power-related losses are systematically quantified. Loss-minimal dispatch is assessed using heuristic optimal power flow. Relevance of findings is demonstrated for the application of reducing system losses based on reactive power control of WPs in closed-loop optimal power flow schemes. It is shown that non-consideration of WP losses may lead to dispatch decisions where the increase in WP losses outweighs the achieved loss reduction in the 110kV system by 400%. The study facilitates comparing reactive power ancillary services from WPs to that of other technologies from an economic perspective. It concludes by a benchmarking overview of pros and cons of modelling alternatives. Copyright (c) 2017 John Wiley & Sons, Ltd.
机译:在电力系统潮流研究中,通常完全忽略风电场(WP)的损耗,因为WP必须提供无功功率作为免费的辅助服务。大大简化的WP损耗估算也很普遍。普遍的损耗建模方法可能会导致相当大的,迄今为止通常被忽略的无功功率分配效率低下。本文的创新在于证明这一点,并提出一种结合了速度,易用性和准确性的替代建模方法。计算基于连接到110kV的通用WP。一次使用无齿轮永磁同步发电机进行仿真,一次使用双馈感应发电机进行仿真。这样,首次系统地量化了在计算与无功功率有关的损失时忽略风力发电机类型之间差异的后果。使用启发式最佳潮流评估最小损耗调度。研究结果的相关性被证明可用于在闭环最佳潮流方案中基于WP的无功功率控制来减少系统损耗。结果表明,不考虑WP损耗可能导致调度决策,其中WP损耗的增加量比110kV系统中实现的损耗减少量大400%。该研究有助于从经济角度比较WP和其他技术的无功辅助服务。最后以基准测试概述了建模替代方案的优缺点。版权所有(c)2017 John Wiley&Sons,Ltd.

著录项

  • 来源
    《Wind Energy》 |2017年第7期|1291-1309|共19页
  • 作者

    Kaempf E.; Braun M.;

  • 作者单位

    Fraunhofer IWES, Konigstor 59, D-34119 Kassel, Germany|Univ Kassel, Energy Management & Power Syst Operat, Wilhelmshoher Allee 73, D-34121 Kassel, Germany;

    Fraunhofer IWES, Konigstor 59, D-34119 Kassel, Germany|Univ Kassel, Energy Management & Power Syst Operat, Wilhelmshoher Allee 73, D-34121 Kassel, Germany;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    reactive power provision; wind park grid integration; ancillary services; voltvar control; system economics;