A field study was performed in a building complex to investigate the extent and sources of lead (Pb) release in tap water and brass material was found to be the main contributor in the very first draw (250 mL). Based on these results, a pilot installation was built to study Pb leaching from old and new faucets in the presence and absence of a connection to Cu piping. Four water quality conditions were tested: i) no treatment; ii) addition of 0.8 mg P/L of orthophosphate; iii) pH adjustment to 8.4; and iv) adjustment to a higher chloride to sulfate mass ratio (CSMR; ratio from 0.3 to 2.9). Pb concentrations in samples taken from the faucets without treatment ranged from 1 to 52 ng/L, with a mean of 11 ng/L. The addition of orthophosphate @ 0.8 mg P/L (OrthoP) was the most effective treatment for all types of faucets tested. On average, OrthoP reduced mean Pb leaching by 41%, and was especially effective for new double faucets (70%). In the presence of orthophosphates, the relative proportion of particulate Pb (Pbpart) (>0.45 μm) increased from 31% to 54%. However, OrthoP was not efficient to reduce Zn release. The higher CSMR condition was associated with greater dezincification of yellow brass but not of red brass. Corrosion control treatment influenced Pb concentration equilibrium, directly impacting maximal exposure. Significantly higher Pb release (3 fold) was observed for 1 of the 8 faucets connected to Cu exposed to high CSMR water, suggesting the presence of galvanic corrosion.
机译:在建筑群中进行了现场研究,以调查自来水中铅(Pb)释放的程度和来源,发现黄铜材料是第一次抽水(250 mL)的主要原因。根据这些结果,建造了一个试验装置,以研究在有无铜管连接的情况下新旧水龙头中铅的浸出。测试了四个水质条件:i)未经处理; ii)加入0.8 mg P / L正磷酸盐; iii)将pH调节至8.4; iv)调整到更高的氯化物与硫酸盐质量比(CSMR;比例从0.3到2.9)。未经处理的水龙头中样品中的铅浓度范围为1到52 ng / L,平均为11 ng / L。以0.8 mg P / L(OrthoP)添加正磷酸盐是所有测试水龙头中最有效的处理方法。平均而言,OrthoP将平均铅的浸出量降低了41%,对于新型双龙头特别有效(70%)。在正磷酸盐的存在下,微粒Pb(Pbpart)(> 0.45μm)的相对比例从31%增加到54%。但是,OrthoP不能有效减少锌的释放。较高的CSMR条件与黄色黄铜的脱锌作用更大,而红色黄铜的脱锌作用更大。腐蚀控制处理影响了Pb浓度平衡,直接影响最大暴露量。与暴露于高CSMR水的铜连接的8个水龙头中,有1个的Pb释放量显着较高(3倍),表明存在电化腐蚀。

著录项

  • 来源
    《Water Research》 |2012年第16期|p.5205-5216|共12页
  • 作者单位

    NSERC Industrial Chair on Drinking Water, Ecole Polytechnique de Montreal, Civil, Geological and Mining Engineering, P.O. Box 6079, Station Centre-ville, Montreal, Quebec, Canada H3C 3A7;

    NSERC Industrial Chair on Drinking Water, Ecole Polytechnique de Montreal, Civil, Geological and Mining Engineering, P.O. Box 6079, Station Centre-ville, Montreal, Quebec, Canada H3C 3A7;

    Correctional Service of Canada, 400 Ave Fordyce Cowansville, Quebec, Canada J2K 3N7;

    NSERC Industrial Chair on Drinking Water, Ecole Polytechnique de Montreal, Civil, Geological and Mining Engineering, P.O. Box 6079, Station Centre-ville, Montreal, Quebec, Canada H3C 3A7;

    NSERC Industrial Chair on Drinking Water, Ecole Polytechnique de Montreal, Civil, Geological and Mining Engineering, P.O. Box 6079, Station Centre-ville, Montreal, Quebec, Canada H3C 3A7;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    drinking water; corrosion; lead; pilot-study; brass; dezincification; galvanic corrosion; faucet;