At time of commissioning, the Racine, Wisconsin, USA ultrafiltration (UF) membrane treatment system failnshort of meeting its operational goals concerning capacity and chemical cleaning intervals. The systematic optimizationnof this 189-million-litre-per-day (MLD) capacity UF system provided tangible operational benefits, which included an30-percent reduction in power use, a 50-percent reduction in chlorine chemical use, a 36-percent reduction in citric acidnuse and a simultaneous 7-percent increase in net treatment capacity of the system. In addition, the optimization programnreduced the level of buildup of foulants on the surface of the membranes. This paper summarizes the optimizationnprocedures followed at Racine, discussing how similar measures may be applicable to other water treatment facilities.
机译:在调试时,美国威斯康星州拉辛的超滤(UF)膜处理系统未能达到其有关容量和化学清洗间隔的操作目标。每天1.89亿升(MLD)的超滤系统的系统优化n提供了明显的运营收益,其中包括电力消耗减少30%,氯化学消耗减少50%,氯化学消耗减少36%柠檬酸,同时使系统的净处理能力提高7%。另外,优化程序降低了污垢在膜表面上的堆积水平。本文总结了Racine遵循的优化程序,并讨论了类似的措施如何适用于其他水处理设施。