首页> 外文期刊>Solar Energy >Night ventilation control strategies in office buildings
【24h】

Night ventilation control strategies in office buildings

机译:办公大楼的夜间通风控制策略

获取原文
获取原文并翻译 | 示例
       

摘要

In moderate climates night ventilation is an effective and energy-efficient approach to improve the indoor thermal environment for office buildings during the summer months, especially for heavyweight construction. However, is night ventilation a suitable strategy for office buildings with lightweight construction located in cold climates? In order to answer this question, the whole energy-consumption analysis software EnergyPlus was used to simulate the indoor thermal environment and energy consumption in typical office buildings with night mechanical ventilation in three cities in northern China. The summer outdoor climate data was analyzed, and three typical design days were chosen. The most important factors influencing night ventilation performance such as ventilation rates, ventilation duration, building mass and climatic conditions were evaluated. When night ventilation operation time is closer to active cooling time, the efficiency of night ventilation is higher. With night ventilation rate of 10 ach, the mean radiant temperature of the indoor surface decreased by up to 3.9 ℃. The longer the duration of operation, the more efficient the night ventilation strategy becomes. The control strategies for three locations are given in the paper. Based on the optimized strategies, the operation consumption and fees are calculated. The results show that more energy is saved in office buildings cooled by a night ventilation system in northern China than ones that do not employ this strategy.
机译:在中等气候下,夜间通风是一种有效且节能的方法,可以在夏季改善办公楼的室内热环境,特别是对于重型建筑。但是,对于在寒冷气候中具有轻型结构的办公楼,夜间通风是否是合适的策略?为了回答这个问题,使用了整个能耗分析软件EnergyPlus来模拟华北三个城市夜间机械通风的典型办公大楼的室内热环境和能耗。分析了夏季室外气候数据,并选择了三个典型的设计日。评估了影响夜间通风性能的最重要因素,例如通风速率,通风持续时间,建筑质量和气候条件。夜间通风运行时间接近主动冷却时间时,夜间通风效率更高。夜间通风速度为10 ach时,室内表面的平均辐射温度降低了3.9℃。操作时间越长,夜间通风策略就越有效。本文给出了三个位置的控制策略。基于优化策略,计算运营消耗和费用。结果表明,与没有采用这种策略的办公楼相比,在中国北方通过夜间通风系统冷却的办公楼可以节省更多的能源。

著录项

  • 来源
    《Solar Energy》 |2009年第10期|1902-1913|共12页
  • 作者单位

    School of Municipal and Environmental Engineering, Harbin Institute of Technology, Nangang District.Haihe road, No. 202, 2nd campus in HIT, Mailbox No. 2644, Harbin 150090, China;

    School of Municipal and Environmental Engineering, Harbin Institute of Technology, Harbin 150090, China;

    School of Municipal and Environmental Engineering, Harbin Institute of Technology, Harbin 150090, China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);美国《生物学医学文摘》(MEDLINE);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    control strategy; mechanical night ventilation; parameter analyses; energy efficiency; cold climate;

    机译:控制策略;机械夜间通风;参数分析能源效率;寒冷的气候;