This paper analyzes stability conditions and design requirements for the control parameters in droop-controlled inverters. The analysis focusses on a single inverter unit with ac (output) filters and interface transformer, as this may be regarded as the elementary component of a distributed generation system. Through a process of thought simplifications and manipulations, the linearized full state-space model is transformed into a unique single-input, single-output system comprising several nested loops. The resulting analytical model in terms of transfer functions has enough “structure” to represent interactions between the different actors of the overall control, such as droop linear and derivative terms, virtual impedance, and voltage controllers. Stability conditions for the corresponding parameters are then derived analytically. Experimental tests are carried out on the complete system to check the reliability of the proposed model.
机译:本文分析了下垂控制逆变器的稳定性条件和控制参数的设计要求。分析集中在具有交流(输出)滤波器和接口变压器的单个逆变器单元上,因为这可以看作是分布式发电系统的基本组件。通过简化思想和操纵过程,将线性化的完整状态空间模型转换为包含多个嵌套循环的唯一单输入单输出系统。由此产生的基于传递函数的分析模型具有足够的“结构”来表示总体控制的不同参与者之间的相互作用,例如,下降线性和微分项,虚拟阻抗和电压控制器。然后通过解析得出相应参数的稳定性条件。在整个系统上进行了实验测试,以检验所提出模型的可靠性。