Piezoelectric Transformer Based Disturbance Monitoring Methodology for High-Voltage Power Supply Lines

机译:基于压电变压器的高压电源线故障监测方法

获取原文
获取原文并翻译 | 示例
           

摘要

We present a novel microsystem methodology to detect voltage and current disturbances in high power distribution lines. Our system employs a custom designed piezoelectric transformer operating at 50/60 Hz, as an alternative to the bulky electromagnetic transformer, to detect disturbances up to few kilohertz. In the frequency range of 10 Hz to 250 Hz, the piezotransformer steps down the 10–150 V input voltage with a linearity of ${pm}{1%}$ . This stepped down piezo output is treated with a signal processing system designed based on frequency composition of the piezo signal, to generate a digital output. A 7-bit digital output from this system reports various types of line disturbances within 3 ms of occurrence. We present details of the proposed system, supported both by numerical simulations and experimental results.
机译:我们提出了一种新颖的微系统方法来检测大功率配电线路中的电压和电流干扰。我们的系统采用定制设计的压电变压器,以50/60 Hz的频率运行,作为笨重的电磁变压器的替代品,可检测高达几千赫兹的干扰。在10 Hz至250 Hz的频率范围内,压电变压器以$ {pm} {1%} $的线性度降低10–150 V输入电压。使用基于压电信号的频率组成设计的信号处理系统处理此降低的压电输出,以生成数字输出。该系统的7位数字输出在发生3毫秒内报告各种类型的线路干扰。我们在数值模拟和实验结果的支持下,提出了拟议系统的详细信息。