首页> 外文期刊>Science, Measurement & Technology, IET >Diagnosis of solid insulation deterioration for power transformers with dissolved gas analysis-based time series correlation
【24h】

Diagnosis of solid insulation deterioration for power transformers with dissolved gas analysis-based time series correlation

机译:基于溶解气体分析的时间序列相关性对电力变压器固体绝缘劣化的诊断

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Dissolved gas analysis (DGA) is a prevailing methodology being widely used to detect incipient faults in power transformers. Although various methods have been developed to interpret DGA results, they may sometimes fail to diagnose precisely, especially when solid insulation deterioration is involved. This study presents a time series correlation technique, in which the sampled data of dissolved gases in the transformer oil are considered as a time series and the series correlation scheme in statistics is adopted to explore and manipulate the fault information. Both the constant and variable characteristic parameters are initially chosen based on analysis in terms of frequency histograms. With quantitative correlation analysis between the constant and variable characteristic parameters, a new criterion for solid insulation diagnosis is thereby proposed, which can be used to diagnose whether solid insulation deterioration is involved in a transformer fault, as well as further distinguish the electrical faults from the thermal ones. According to the proposed technique, explorative tests regarding two power transformers have shown promising results. With regard to the 91 fault samples collected from China Power Grid, the diagnosis accuracies for electrical and thermal faults were 86.5 and 77.7%, respectively, whereas it was 61.5% for the prevailing CO/CO criterion.
机译:溶解气体分析(DGA)是一种流行的方法,已广泛用于检测电力变压器中的初期故障。尽管已开发出多种方法来解释DGA结果,但有时可能无法准确诊断,尤其是当涉及到固体绝缘劣化时。本研究提出了一种时间序列相关技术,其中将变压器油中溶解气体的采样数据视为一个时间序列,并采用统计中的序列相关方案来探索和处理故障信息。根据频率直方图,首先根据分析选择恒定和可变特征参数。通过对恒定和可变特征参数之间的定量相关性分析,提出了一种用于固体绝缘诊断的新标准,该标准可用于诊断变压器故障中是否涉及固体绝缘劣化,以及进一步区分电气故障与变压器故障。热的。根据提出的技术,对两个电源变压器的探索性测试显示出令人鼓舞的结果。从中国电网收集的91个故障样本中,电气和热故障的诊断准确度分别为86.5和77.7%,而现行的CO / CO标准的诊断准确度为61.5%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号