首页> 外文期刊>Science, Measurement & Technology, IET >Investigations of dielectric monitoring on an energised transformer oil–paper insulation system
【24h】

Investigations of dielectric monitoring on an energised transformer oil–paper insulation system

机译:带电变压器油纸绝缘系统的介电监测研究

获取原文
获取原文并翻译 | 示例
           

摘要

Frequency domain spectroscopy (FDS) is being used to assess the insulation condition of oil-paper power transformers. However, it has to date only been implemented on de-energised transformers, which requires the transformers to be shut down for an extended period and may cause significant costs. To solve this issue, a newly improved monitoring method based on the FDS principle is proposed to implement the dielectric measurement on energised transformers. Moreover, a chirp waveform excitation and its novel processing method are introduced. Compared with the conventional FDS results, dielectric results from the energised insulation system have higher tanδ values because of the increased losses. To further understand the insulation ageing process, the effects of the geometric capacitance are removed from the measured imaginary admittance of the insulation system to enhance the ageing signature. The resulting imaginary admittance is then shown to correlate well with the central time constant in return voltage measurements results. The proposed methods address the issues on techniques used on energised transformers and provide a clue for on-line FDS diagnostic application.
机译:频域光谱法(FDS)用于评估油纸电力变压器的绝缘状况。然而,迄今为止,它仅在断电的变压器上实施,这要求将变压器关闭很长一段时间,并可能导致大量成本。为解决这一问题,提出了一种基于FDS原理的改进监测方法,用于对带电变压器进行介电测量。此外,还介绍了线性调频波形激励及其新颖的处理方法。与传统的FDS结果相比,通电的绝缘系统产生的介电结果由于损耗增加而具有更高的tanδ值。为了进一步了解绝缘老化过程,从测量的绝缘系统虚构导纳中去除了几何电容的影响,以增强老化特征。在返回电压测量结果中,所得的虚数导纳随后显示与中心时间常数良好相关。所提出的方法解决了在通电变压器上使用的技术问题,并为在线FDS诊断应用提供了线索。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号