首页> 外文期刊>Renewable & Sustainable Energy Reviews >Shunt fault analysis methodology for power distribution networks with inverter-based distributed energy resources of the Korea Electric Power Corporation
【24h】

Shunt fault analysis methodology for power distribution networks with inverter-based distributed energy resources of the Korea Electric Power Corporation

机译:韩国电力公司逆变基于分布式能源配电网络分流故障分析方法

获取原文
获取原文并翻译 | 示例
           

摘要

Recently, the interconnection of distributed energy resources (DERs) has been observed to hinder the reliability of power supply. To solve this problem, the Korea Electric Power Corporation (KEPCO) has attempted to develop a practical fault analysis methodology for DERs that can be applied to distribution management system (DMS). This novel methodology to analyze the impacts of various DERs during shunt faults is presented in this paper. First, the basic concepts behind the proposed methodology are introduced. Then, the fault analysis methodology is introduced to determine the contributions of balanced and unbalanced DERs during shunt faults. Finally, the accuracy and feasibility of the proposed method are confirmed using SIMULINK and the IEEE 30-bus system, respectively. Based on the analyses, the proposed methodology is expected to be integrated with the rapidly developing distribution automation and management system of the KEPCO.
机译:最近,已经观察到分布式能源(DER)的互连来阻碍电源的可靠性。为了解决这个问题,韩国电力公司(Kepco)试图为可以应用于分销管理系统(DMS)的DER开发实际的故障分析方法。本文提出了这种新的方法来分析分流器中各种DER的影响。首先,介绍了所提出的方法背后的基本概念。然后,引入了故障分析方法,以确定分流故障期间平衡和不平衡的额度的贡献。最后,使用Simulink和IEEE 30-Bus系统确认所提出的方法的准确性和可行性。基于分析,预计建议的方法将与Kepco的快速开发的分销自动化和管理系统一体化。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号