This paper proposes a modelling and simulation process for assessing the energy absorption capability of metal oxide varistor (MOV) surge arresters used for lightning protection of wind turbines electrical systems situated in wind farms, when exposed to multiple lightning strokes. A section of an existing wind farm, suitable for lightning transient overvoltage analysis is implemented in the Electromagnetic transients programme-Alternative transients programme (EMTP-ATP) environment and modelled as a test system for analysing the energy absorbed by the medium voltage surge arresters when multiple lightning strokes are terminated on one of the blade of the wind turbines. Two well-established sets of multiple lightning current parameters are employed in the EMTP-ATP simulations; the natural downward negative multiple lightning strokes recommended by CIGRE TB 549 (2013) and the downward positive multiple lightning strokes recommended by IEC 61400-24-2010 for lightning protection level one (LPL1). The results show that the subsequent stroke causes the surge arresters to absorbed less than ten percent additional energy compared to that of the first stroke. This comparative analysis could be found beneficial when designing lightning overvoltage protection system and for selecting the most cost effective and optimal energy absorption capabilities of the surge arresters for the intended wind farms. (C) 2015 Elsevier Ltd. All rights reserved.
机译:本文提出了一种建模和仿真过程,用于评估暴露在多个雷击中的风力发电场电气系统中用于雷电保护的金属氧化物变阻器(MOV)避雷器的能量吸收能力。在电磁暂态程序-交替暂态程序(EMTP-ATP)环境中,实施了适用于雷电暂态过电压分析的现有风电场的一部分,并将其建模为测试系统,用于分析多个中压避雷器吸收的能量雷击终止于风力涡轮机的叶片之一上。在EMTP-ATP模拟中,采用了两套完善的多重雷电流参数集。 CIGRE TB 549(2013)建议的自然向下负多次雷击和IEC 61400-24-2010建议的一级防雷(LPL1)建议向下自然雷击。结果表明,与第一个冲程相比,随后的冲程导致电涌放电器吸收的能量少于百分之十。在设计雷电过电压保护系统以及为预期的风电场选择电涌放电器的最具成本效益和最佳能量吸收能力时,可以发现这种比较分析是有益的。 (C)2015 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号