首页> 外文期刊>日本建築学会環境系論文集 >多数室換気に局所相似モデルを適用した場合の通風量予測の精度検証及び戸建住宅の通風量解析への適用: 通風時の換気量予測法に関する研究(第4報)
【24h】

多数室換気に局所相似モデルを適用した場合の通風量予測の精度検証及び戸建住宅の通風量解析への適用: 通風時の換気量予測法に関する研究(第4報)

机译:将局部相似模型应用于多房间通风并将其应用于独立房通风量分析时,通风量预测的准确性验证:通风期间的通风量预测方法研究(第四次报告)

获取原文
获取原文并翻译 | 示例
       

摘要

In the paper, the COMIS-LDSM program was developed that the COMIS code was revised to calculate the discharge coefficients and airflow rates at inflow and outflow openings for arbitrary wind direction. Wind tunnel experiments were performed to validate the prediction accuracy of ventilation flow rates using the COMIS-LDSM and the conventional method. The conventional method overestimated the ventilation flow rates compared to those by COMIS-LDSM, especially when the approaching flow was not normal to the upwind openings. The simulation study was also carried out to calculate ventilation flow rates at a typical detached house in Tokyo in the intermediate season. The cumulative air change rates in the detached house calculated by COMIS-LDSM were predicted by reduction of 4% compared with the conventional method.%本報では,換気回路網ソフトCOMISに局所相似モデルを組み込んだCOMIS-LDSMプログラムを作成し,通風量予測の精度検証と戸建住宅の通風量解析を行った。その結果として得られた主な知見は以下の通りである。(1)局所相似モデルを用いて2室の通風模型で通風量の予測精度を検討した。局所相似モデルは,流量係数を一定とした従来法に比べて,風向角が開口部に正対しない場合に通風量の予測精度が向上した。
机译:在本文中,开发了COMIS-LDSM程序,对COMIS代码进行了修改,以计算任意风向的进风口和出风口的排放系数和气流速率。使用COMIS-LDSM和常规方法进行了风洞实验,以验证通风流量的预测准确性。与COMIS-LDSM相比,传统方法高估了通风流速,特别是当进风与上风口不垂直时。还进行了模拟研究,以计算中期季节东京典型的独立式住宅的通风流量。通过COMIS-LDSM计算的独立式住宅中的累积空气变化率与传统方法相比减少了4%。%本报では,换気回路网ソフトトートISISそ,结果与して得デ主を知见は以下の通りである。(1)局所相似モデルを用いて2室の通风模型局所相似默デルは,流量系数を一定とした従来法に比べて,风向角が开口部に正対しない场合に通风量の予测精度が向上した。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号