首页> 外文期刊>IEEE Transactions on Power Delivery >Results of an investigation on the overvoltages due to a vacuum circuit-breaker when switching an HV motor
【24h】

Results of an investigation on the overvoltages due to a vacuum circuit-breaker when switching an HV motor

机译:对切​​换高压电动机时由真空断路器引起的过电压的调查结果

获取原文
获取原文并翻译 | 示例
           

摘要

The results of a study of overvoltages arising when an HV motor is switched by a vacuum circuit breaker are presented. A laboratory test circuit was devised that would reproduce the actual network conditions in a generating plant, and special measurement and acquisition systems were used to enable the switching-surge amplitude and waveform to be recorded with accuracy. Statistical processing of the data was followed by estimation of the probability of occurrence of overvoltages and by evaluation of the number of the surges impinging on the motor-winding during its operating life. The results are discussed, and a number of conclusions are drawn.
机译:给出了研究由真空断路器切换高压电动机时产生的过电压的结果。设计了一个实验室测试电路,可以再现发电厂的实际网络状况,并使用特殊的测量和采集系统来准确记录开关浪涌的幅度和波形。对数据进行统计处理之后,估算过电压发生的可能性,并评估在其工作寿命期间冲击在电机绕组上的电涌数。讨论了结果,并得出了许多结论。