The paper presents results of the studies on overvoltages generated while switching unloaded medium voltage (MV) power cable lines by a vacuum switch. The studies were carried out while switching real MV cable lines and their physical models. It has been found that overvoltages and overcurrents are generated during switching, and that under certain conditions they may reach significant values. These values depend on the source side circuit parameters, on kinematics vacuum switch parameters as well as on parameters of a switched cable line.
机译:本文介绍了通过真空开关切换无载中压(MV)电力电缆线路时产生的过电压的研究结果。在切换实际中压电缆线及其物理模型时进行了研究。已经发现,在切换期间会产生过电压和过电流,并且在某些条件下它们可能达到明显的值。这些值取决于源侧电路参数,运动学真空开关参数以及交换电缆线的参数。