The diagnosis of abnormal conditions at current-conducting contacts by measuring the metal-enclosure vibrations of gas-insulated switchgear was studied experimentally and theoretically. Vibrations appeared when current flowed through artificially simulated abnormal contacts. Vibration peaks existed at frequencies which were integral values times the current frequency, especially between 400 Hz and 2 kHz. Vibration peak values increased as contact voltage increased above 400 Hz. Contact voltage waveforms in the stable state were distorted and their top peaks became sharp as the contact voltage increased. The reason for the distortion was the temperature rise which accompanied the alternating current change.
机译:实验和理论上研究了通过测量气体绝缘开关设备的金属外壳振动来诊断导电端子的异常情况。当电流流过人工模拟的异常触点时会出现振动。振动峰的频率是当前频率的整数倍,特别是在400 Hz和2 kHz之间。振动峰值随着接触电压增加到400 Hz以上而增加。稳定状态下的接触电压波形会失真,并且随着接触电压的增加,其峰值会变得尖锐。变形的原因是伴随交流电变化的温度上升。