首页> 外文期刊>IEEE Transactions on Power Delivery >Seismic behaviour of toughened glass station post insulators for 800 kV networks
【24h】

Seismic behaviour of toughened glass station post insulators for 800 kV networks

机译:钢化玻璃站柱绝缘子在800 kV网络中的抗震性能

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The results of tests on 800 kV toughened glass post insulators are presented and analytical study to define their dynamic behavior when associated with connections and a supporting chassis under extreme service conditions (earthquake, short-circuit) is described. The findings show that the performance of toughened glass post insulators under high-amplitude dynamic loads permits even the most stringent specifications to be satisfied with a high safety margin. Under forced vibrations, the acceleration at the top of the insulator necessary to cause breakage was 5.6 g (g=9.81 m/s/sup 2/), which is at least three times larger than that required by specifications for Venezuela and the US West Coast.
机译:给出了在800 kV钢化玻璃立柱式绝缘子上的测试结果,并进行了分析研究,以定义其在极端工作条件(地震,短路)下与连接件和支撑底盘相关联时的动态行为。研究结果表明,钢化玻璃支柱绝缘子在高振幅动态载荷下的性能甚至可以满足最严格的规格,并具有很高的安全裕度。在强制振动下,导致破裂所需的绝缘子顶部的加速度为5.6 g(g = 9.81 m / s / sup 2 /),至少是委内瑞拉和美国西部规范要求的三倍。海岸。