首页> 外文期刊>IEEE Transactions on Power Delivery >Withstand voltage characteristics of insulator string covered with snow or ice
【24h】

Withstand voltage characteristics of insulator string covered with snow or ice

机译:冰雪覆盖的绝缘子串的耐压特性

获取原文
获取原文并翻译 | 示例
           

摘要

The authors describe the results of an investigation into the withstand voltage characteristics of an insulator string covered with snow or ice and the application of these results to the insulation design and maintenance of a transmission line in a heavy snow area. It was found that the characteristics of withstand voltage were affected by the specific gravity of snow, the conductivity of water melted from snow, the height of snow, and the ratio of snow-covered length. The lightning impulse flashover voltage of insulator string covered with snow is much lower than that of nonsnow-covered insulator, indicating that the efficiency of lightning protection greatly decreases under snowing conditions. When transmission lines pass through a heavy snow area, an extension of the transmission system fault is feared in 54 and 275 kV transmission lines because the existing insulator string length does not have sufficient dielectric strength for temporary AC overvoltage and switching surge.
机译:作者描述了调查被雪或冰覆盖的绝缘子串的耐压特性的结果,并将这些结果应用于大雪地区的输电线路的绝缘设计和维护。研究发现,耐压特性受雪比重,雪融水的电导率,雪高和雪长比的影响。积雪覆盖的绝缘子串的雷电冲击击穿电压远低于未覆雪的绝缘子,这表明在下雪条件下,防雷效率大大降低。当输电线经过大雪地区时,由于54 kV和275 kV输电线存在着绝缘子串长度不足以承受暂时交流过电压和开关浪涌的绝缘强度的问题,因此担心输电系统故障会扩大。