As part of the development of an advanced, more consistently accurate transmission line fault location system (AFLS), an evaluation of the performance and requirements for voltage and current input transducers was made. Measurements of current transformer and burdens were made, and computer models of the steady-state and transient responses were developed. Burdens from the electromechanical relaying and metering equipment in the secondary circuits were found to be large enough to cause transient distortion of the current waveforms for some fault causes, and would not meet the stringent requirements for an AFLS. A recommendation was made to place the AFLS in the primary relaying circuits, where electronic relays having low burdens are installed.
机译:作为开发先进的,始终如一的精确传输线故障定位系统(AFLS)的一部分,对电压和电流输入传感器的性能和要求进行了评估。测量了电流互感器和负载,并建立了稳态和瞬态响应的计算机模型。发现次级电路中机电继电和计量设备的负担足够大,以至于由于某些故障原因而导致电流波形的瞬态失真,并且不能满足AFLS的严格要求。有人建议将AFLS放置在安装有低负荷电子继电器的主继电器电路中。