The single-phase exciting-current test can be used to detect undesirable conditions in single- and three-phase transformers. Normally the test results are analyzed by comparing currents between all three phases in a given transformer and between similar single-phase units. Certain problems, however, can be detected on the basis of current change when the measurements are performed on different load tap changer positions. Accordingly, understanding how the load tap changer affects the current magnitude of individual phases is essential for developing proper analysis. This paper identifies twelve patterns of test result behavior, and an attempt is made to show different load tap changer designs as they affect the measurement. The test results and test circuit diagrams are given. The derived patterns will be implemented in a DOS-based expert system in combination with a data acquisition system which is currently used in the field by more than 80 utilities.
机译:单相励磁电流测试可用于检测单相和三相变压器中的不良条件。通常,通过比较给定变压器中所有三相之间以及相似单相单元之间的电流来分析测试结果。但是,当在不同的有载分接开关位置上执行测量时,可以根据电流变化检测某些问题。因此,了解负载分接开关如何影响各个相的电流幅度对于进行正确的分析至关重要。本文确定了测试结果行为的十二种模式,并尝试显示不同的有载分接开关设计,因为它们会影响测量。给出了测试结果和测试电路图。派生的模式将在基于DOS的专家系统中与数据采集系统结合起来实施,该系统目前已被80多个公用事业公司在该领域使用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号