This paper presents the development of a newapproach for diagnosing the occurrence of inter-turnshort-circuits in the windings of three-phase transformers,which is based on the on-line monitoring of the on-loadexciting current Park's Vector patterns. Experimental andsimulated results demonstrate the effectiveness of theproposed technique for detecting winding inter-turn insulationfaults in operating three-phase transformers.
机译:本文提出了一种新的方法,用于诊断三相变压器绕组中匝间短路,该方法是基于对负载励磁电流Park矢量模式的在线监测。实验和仿真结果证明了该技术在检测运行中的三相变压器中绕组匝间绝缘故障中的有效性。