Gapless zinc oxide (ZnO) transmission line arresters were fault tested under simulated field service conditions to address important reliability issues associated with their application. Specific reliability issues addressed were: (1) failure mode or pressure relief capabilities; (2) the ability of the arrester fault isolation device to isolate a faulted arrester from the system while simulating a high speed line reclosing operation; and (3) verification that the evolving fault is restricted to the faulted phase only and does not involve adjacent unfaulted phases. An important and unique aspect of this test was to demonstrate how the complete assembly, made up of an actual 100 kV tower structure, arrester and associated elements, would perform by documenting results for each of the three reliability issues noted. Test results address important user application issues impacting system reliability and suggest potential focus areas for future standards development work.
机译:无间隙氧化锌(ZnO)传输线避雷器在模拟现场服务条件下进行了故障测试,以解决与其应用相关的重要可靠性问题。解决的特定可靠性问题是:(1)故障模式或泄压能力; (2)避雷器故障隔离装置在模拟高速线路重合闸操作时将故障避雷器与系统隔离的能力; (3)验证正在发展的断层仅限于断层相,并且不涉及相邻的未断层相。该测试的一个重要而独特的方面是,通过记录所记录的三个可靠性问题的每一个的结果,来演示由一个实际的100 kV塔架结构,避雷器及相关元件组成的完整组件的性能。测试结果解决了影响系统可靠性的重要用户应用问题,并提出了未来标准开发工作的潜在重点领域。