首页> 外文期刊>IEEE Transactions on Power Delivery >Self-generated overvoltages due to open-phasing of ungrounded-wye delta transformer banks
【24h】

Self-generated overvoltages due to open-phasing of ungrounded-wye delta transformer banks

机译:由于未接地WWE三角洲变压器组的断相而产生的自生过电压

获取原文
获取原文并翻译 | 示例
           

摘要

Disconnecting one phase of an ungrounded-wye delta transformer bank from the source can result in severe overvoltages due to neutral shift and ferroresonance. Neutral shift overvoltages are quantified and their impact on metal-oxide surge arresters are evaluated. Ferroresonance is shown by test data to occur when low-loss banks, 15 kV and higher, are open phased. Design and operating practices to eliminate or mitigate these self-generated overvoltages are discussed.
机译:由于中性移位和铁磁谐振,将未接地的三角形变压器组的一相与电源断开会导致严重的过电压。对空档过电压进行量化,并评估其对金属氧化物电涌放电器的影响。测试数据表明,铁磁谐振是在15 kV及更高的低损耗组断相时发生的。讨论了消除或减轻这些自生过电压的设计和操作方法。