EHV transformer bank unbalance: practical issues and solutions

机译:超高压变压器组的不平衡:实际问题和解决方案

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

An unconventional tap configuration has been implemented in AEP's South Canton 765/345/34.5 kV 3*500 MVA transformer bank to counter the combined effects of impedance mismatch within the bank and the natural unbalance of the EHV transmission system. These effects manifest themselves as unequal phase voltages and loadings and as elevated neutral and tertiary circulating currents in the bank, capable of reaching high magnitudes during heavy loading conditions. This paper describes the South Canton bank unbalance, the concerns it raised, and the actions taken by AEP to control its possible adverse effects on the integrity and operation of the South Canton Station (USA) facilities.
机译:AEP的South Canton 765/345 / 34.5 kV 3 * 500 MVA变压器组采用了非常规抽头配置,以抵消组内阻抗失配和EHV传输系统自然不平衡的综合影响。这些影响表现为相电压和负载不相等,以及银行中中性和三次循环电流的升高,在重负载条件下能够达到较高的幅值。本文介绍了南广州银行的不平衡状况,所引起的担忧以及AEP为控制其可能对南广州车站(美国)设施的完整性和运行造成的不利影响而采取的措施。