首页> 外文期刊>IEEE Transactions on Power Delivery >Harmonic evaluation of Benmore converter station when operated as a group connected unit
【24h】

Harmonic evaluation of Benmore converter station when operated as a group connected unit

机译:作为一组连接单元运行时,本莫尔换流站的谐波评估

获取原文
获取原文并翻译 | 示例
           

摘要

Three-phase harmonic measurements of a group connected generator-HVDC power converter unit were recently carried out at the Benmore end of the New Zealand HVDC link. This paper describes the test measurement procedures, the set up and configuration of the CHART instrumentation and presents the results which include measured waveforms and their harmonic contents in sequence components for a range of DC line currents. Dynamic simulation accurately predicts the harmonic current contents. The generator harmonic impedances are estimated from the measured and simulated terminal voltages and currents. The generator harmonic ratings for direct connections are also investigated.
机译:最近在新西兰HVDC链路的Benmore末端对一组连接的发电机-HVDC电力转换器单元进行了三相谐波测量。本文描述了测试测量程序,CHART仪器的设置和配置,并给出了结果,其中包括在一系列直流线路电流中,测量的波形及其谐波含量在顺序分量中的分布。动态仿真可准确预测谐波电流含量。发电机谐波阻抗是根据测量和模拟的端子电压和电流估算的。还研究了直接连接的发电机谐波额定值。