首页> 外文期刊>IEEE Transactions on Power Delivery >Radio frequency signal transmission on medium voltage powerdistribution lines
【24h】

Radio frequency signal transmission on medium voltage powerdistribution lines

机译:中压配电线上的射频信号传输

获取原文
获取原文并翻译 | 示例
           

摘要

A series of tests measuring HF signal attenuation were performednon a de-energized 15 kV three-phase power distribution feeder. Thenfeeder consisted of a U-shaped line measuring approximately 208 m innlength with varying line geometry around the circuit. RF signals in thenrange of 2 to 30 MHz were injected in one phase of the feeder and thenpropagated responses were measured at two locations along the feeder.nTests were conducted with and without shunt power equipmentn(distribution transformers, arresters and capacitors) connected to thenfeeder. The characteristic line impedance of different line geometriesnwas calculated by analytical means and found to be consistent withnexperimental results. Attenuation and characteristic impedance werenfound to be relatively constant at frequencies between 15 and 30 MHznwith minimal influence from line geometry and power equipment placement
机译:在未通电的15 kV三相配电馈线上进行了一系列测量HF信号衰减的测试。然后,送料器由一条U型线组成,该线的长度约为208 m,电路周围的线几何形状各不相同。然后在馈线的一相中注入2至30 MHz范围内的RF信号,然后在馈线的两个位置处测量传播的响应。n在有无分流电源设备(配电变压器,避雷器和电容器)连接到馈线上的情况下进行了测试。通过分析方法计算出不同线形的特征线阻抗,发现与实验结果一致。衰减和特性阻抗在15至30 MHzn的频率下相对恒定,并且不受线路几何形状和电力设备放置的影响