首页> 外文期刊>IEEE Transactions on Power Delivery >Conducted emissions from FACTS equipment operational within substations $part II
【24h】

Conducted emissions from FACTS equipment operational within substations $part II

机译:在变电站内运行的FACTS设备的传导排放第二部分

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

Electromagnetic interference (EMI) may be caused by the fast switching of thyristors and gate turn-off thyristors (GTOs), which are used in static var compensators (SVCs) and static synchronous compensators (STATCOMs) to control reactive power generation and absorption to and from the transmission system. As a result, high levels of electrical disturbance may be coupled into the electrical ports of auxiliary electronic equipment, and if the levels are above the immunity level of the equipment, maloperation that may lead to a trip can occur. This study sought to measure typical conducted EMI levels in four selected SVC-based and one static synchronous compensator (STATCOM)-based substation. The results and their correlation to the existing IEC 61000-4 EMC Standards series are discussed, and indications of changes to the immunity tests are presented.
机译:晶闸管和栅极关断晶闸管(GTO)的快速切换可能会引起电磁干扰(EMI),这在静态无功补偿器(SVC)和静态同步补偿器(STATCOM)中用于控制无功功率的产生和吸收。从传输系统。结果,高水平的电干扰可能被耦合到辅助电子设备的电端口中,并且如果该水平高于设备的抗干扰水平,则可能发生可能导致跳闸的误操作。这项研究试图测量四个选定的基于SVC的变电站和一个基于静态同步补偿器(STATCOM)的变电站的典型传导EMI电平。讨论了结果及其与现有IEC 61000-4 EMC标准系列的相关性,并给出了抗扰度测试变化的指示。