The remote detection of a transformer internal partial discharge (PD) has been demonstrated using mobile wideband radio-frequency receiving equipment. The PD is externally detectable due to coupling within the transformer tank, causing impulsive signals to be radiated from external connections. A wideband direction-finding technique using a four-antenna array has shown the source of the radiation to be the tertiary winding connections; the radiated impulse has characteristics typical of this method of emission. No other external site of radiation from the transformer was detected. Due to the lack of coupling to the primary and secondary windings, it is believed that the PD is present between the tertiary windings and the core.
机译:已经使用移动宽带射频接收设备演示了对变压器内部局部放电(PD)的远程检测。由于变压器箱内的耦合,可从外部检测PD,从而导致脉冲信号从外部连接辐射出来。使用四天线阵列的宽带测向技术已经表明,辐射源是三次绕组连接。辐射脉冲具有这种发射方法的典型特征。没有检测到来自变压器的其他外部辐射点。由于缺乏与初级绕组和次级绕组的耦合,因此可以认为PD存在于第三级绕组和铁芯之间。