首页> 外文期刊>IEEE Transactions on Power Delivery >Research on Current Commutation Measures for Hybrid DC Circuit Breakers
【24h】

Research on Current Commutation Measures for Hybrid DC Circuit Breakers

机译:混合直流断路器电流换流措施的研究

获取原文
获取原文并翻译 | 示例
       

摘要

The hybrid direct-current circuit breaker (DCCB) consists of a mechanical switch (MS) branch and a static DCCB branch. Once a short-circuit fault is detected, the current should commutate from the MS branch to the static DCCB branch first. In this paper, two current commutation measures have been investigated. A hybrid DCCB prototype with current commutated by the arc voltage of the SF6 switch is developed. Based on the prototype, current commutation and interruption tests have been carried out. The results show the current of 3.4 kA can be commutated within 2.4 ms, and be interrupted within 6 ms. Then, a current commutation drive circuit (CCDC) is proposed as the other current commutation measure. Equivalent current commutation tests have been carried out. The results show with the CCDC, both positive current and negative current can be commutated within tens of microseconds. Using a CCDC in series with a mechanical vacuum switch as the MS branch, a 44 kV/3.4 kA hybrid DCCB prototype is developed. Based on the prototype, current commutation and interruption tests are carried out. According to the results, the current of 3.4 kA can be commutated within 100 μs, and be interrupted within 2 ms.
机译:混合式直流断路器(DCCB)由机械开关(MS)分支和静态DCCB分支组成。一旦检测到短路故障,电流应首先从MS支路换向静态DCCB支路。本文研究了两种目前的换向措施。开发了一种混合DCCB原型,其电流通过SF6开关的电弧电压进行转换。基于原型,进行了当前的换向和中断测试。结果表明,3.4 kA的电流可在2.4 ms内整流,并在6 ms内中断。然后,提出了电流换向驱动电路(CCDC)作为另一种电流换向措施。已经进行了等效电流换向测试。结果表明,使用CCDC,正电流和负电流都可以在数十微秒内转换。使用串联的CCDC和机械真空开关作为MS分支,开发了44 kV / 3.4 kA混合DCCB原型。基于原型,进行了电流换相和中断测试。根据结果​​,可以在100μs内对3.4 kA的电流进行换向,并在2 ms内将其中断。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号