Different HVDC grid types and the respective protection options are discussed. An earthed bipole HVDC grid was modeled in PSCAD, and using simulation results, the necessity of di/dt limiting inductors to contain the rise of fault currents within the capacity of current hybrid dc breakers is demonstrated. The impact of different inductor sizes on current rise was studied. A fault detection and localization scheme using the rate of change of voltage measured at the line side of the di/dt limiting reactors is proposed. The protection system was modeled and tested under different fault types and locations. The results show that the proposed method of HVDC grid protection is feasible using the current hybrid dc breaker technology. A systematic procedure for setting the necessary protection threshold values is also demonstrated.
机译:讨论了不同的HVDC电网类型和相应的保护选项。在PSCAD中对接地的双极HVDC电网进行了建模,并使用仿真结果证明了di / dt限制电感器将故障电流的上升限制在电流混合直流断路器容量之内的必要性。研究了不同电感尺寸对电流上升的影响。提出了一种利用在di / dt限制电抗器的线路侧测得的电压变化率的故障检测和定位方案。在不同的故障类型和位置下对保护系统进行了建模和测试。结果表明,采用当前的混合直流断路器技术,提出的高压直流输电电网保护方法是可行的。还演示了用于设置必要的保护阈值的系统过程。