首页> 外文期刊>IEEE Transactions on Power Delivery >Single-Line-to-Ground Fault Feeder Selection Considering Device Polarity Reverse Installation in Resonant Grounding System
【24h】

Single-Line-to-Ground Fault Feeder Selection Considering Device Polarity Reverse Installation in Resonant Grounding System

机译:考虑谐振接地系统中的设备极性反向安装的单线到接地故障馈线选择

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

This paper proposes a new method to select single-line-to-ground (SLG) fault feeder in resonant grounding power distribution system based on compensation characteristic of extinction coil in different frequencies. The proposed method is insusceptible to the influence of device polarity reverse installation. Firstly, through analyzing the zero sequence equivalent circuit under a SLG fault, the difference of zero sequence current share in fundamental frequency and second-harmonic frequency is investigated. And then, according to the change of current share (CCS), fault feeder selection criterion and steps are established. Finally, numerous simulation tests demonstrate the effectiveness of the proposed method in identifying the faulty feeder or the faulty bus. Besides, its reliability is also verified by tests with different system parameters and different fault conditions. Specially, device polarity reverse installation tests and comparisons are also implemented, which shows the advantages of the proposed method in dealing with device polarity reverse installation.
机译:本文提出了一种基于不同频率灭绝线圈的补偿特性选择谐振接地配电系统中的单线到地面(SLG)故障进给器的新方法。所提出的方法是对器件极性反向安装的影响。首先,通过在SLG故障下分析零序等效电路,研究了零序电流份额在基频和二次谐波频率下的差异。然后,根据当前份额(CCS)的变化,建立故障馈线选择标准和步骤。最后,许多模拟测试证明了所提出的方法在识别出故障馈线或故障总线时的有效性。此外,还通过具有不同系统参数和不同故障条件的测试来验证其可靠性。特别地,还实现了设备极性反向安装测试和比较,这表明了在处理设备极性反向安装方面提出的方法的优点。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号