首页> 外文会议>International Conference on Renewable Power Generation >High resistance grounding fault feeder detection in a resonant grounding system based on transient current correlation coefficient comparison
【24h】

High resistance grounding fault feeder detection in a resonant grounding system based on transient current correlation coefficient comparison

机译:基于瞬态电流相关系数比较的谐振接地系统中的高电阻接地故障馈线检测

获取原文

摘要

Because the fault characteristics is not obvious, the high resistance grounding fault feeder selection in a resonant grounding system has always been a hot and difficult problem in the field of power system protection. To solve this problem, the expressions of the transient zero sequence current of each feeder under over-damping and under-damping conditions are obtained based on the transient equivalent circuit of high resistance grounding fault in a resonant grounding system. The correlation degree of the transient zero sequence current between any two feeders is analysed by using the correlation coefficient method, so as to realize the fault feeder selection for high resistance grounding fault. Simulation results of PSCAD software show that this method is not affected by transition resistance, initial phase angle of fault, and has high accuracy and reliability.
机译:由于故障特性不明显,因此在谐振接地系统中的高电阻接地故障进料器选择在电力系统保护领域始终是一个热烈且困难的问题。为了解决这个问题,基于谐振接地系统中的高电阻接地故障的瞬态等效电路获得了在过度阻尼和阻尼条件下的每个进纸器的瞬态零序列电流的表达。通过使用相关系数方法分析任意两个馈线之间的瞬态零序电流的相关程度,以实现高电阻接地故障的故障进料器选择。 PSCAD软件的仿真结果表明,该方法不受过渡电阻,初始故障角度的影响,具有高精度和可靠性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有