摘要

A novel partial discharge (PD) detection method for transformers on site adopting its component as ultra-high frequency (UHF) sensor is proposed. The bushing tap, iron core, and high-voltage (HV) winding can be used as internal UHF sensor for UHF PD detection. The experiments are carried out on an 80-kV transformer model to prove the validity of this method. The results show that the proposed method has good detection sensitivity and anti-disturbance performance, and can measure the PD signals without additional sensor. It solves the problem of the lack of available unused valves for internal UHF sensor installation while the external sensor is susceptible to interference. It provides a novel method with application prospects for PD detection of transformers in field.
机译:提出了一种新的局部放电(PD)用于采用其组件作为超高频(UHF)传感器的现场变压器的局部放电(PD)检测方法。衬套龙头,铁芯和高压(HV)绕组可用作UHF PD检测的内部UHF传感器。实验在80kV变压器模型上进行,以证明这种方法的有效性。结果表明,该方法具有良好的检测灵敏度和抗干扰性能,可以测量没有额外传感器的PD信号。它解决了内部UHF传感器安装缺乏可用的未使用阀门的问题,而外部传感器容易受到干扰。它提供了一种新的方法,用于PD检测现场变压器的应用前景。