首页> 外文期刊>IEEE Transactions on Power Delivery >A new method for real-time monitoring of high-voltage transmission-line conductor sag
【24h】

A new method for real-time monitoring of high-voltage transmission-line conductor sag

机译:高压传输线导线凹陷实时监测的一种新方法

获取原文
获取原文并翻译 | 示例
       

摘要

The amount of power flowing through a high-voltage transmission line is proportional to its voltage and the current flowing through it. To increase power flow without modifying the line to support increased voltage, the current must be increased. There is a limit to this, however, since increasing the current causes the conductor temperature to increase and, hence, the conductors to elongate and sag. In this paper, a method to simply and inexpensively measure the amount of conductor sag and, through simple calculation, the average conductor core temperature is described, and the results of a field test are summarized. The method involves attaching two ends of a grounded wire of high electrical resistance to an appropriate location on each of two transmission-line towers and measuring the current induced on the wire by the nearby transmission-line conductors. Information from this measurement is a critical input to any method for dynamically rating transmission lines.
机译:流过高压传输线的功率量与其电压成比例,电流流过它。为了增加电源而不修改线路以支持增加电压,必须增加电流。然而,存在限制,因为增加电流使导体温度增加,因此,导体伸长和下垂。在本文中,一种简单且廉价地测量导体凹陷量的方法,并且通过简单计算描述平均导体核心温度,并且总结了场测试的结果。该方法涉及将接地线的接地线的两端连接到两个传输线塔上的每一个上的适当位置,并通过附近的传输线导体测量导线上的电流。来自该测量的信息是对动态额定传输线的任何方法的关键输入。