Explosion Prevention and Fire Protection of Transformer: An Analysis of 3 Decades of Indian Experience

机译:变压器的防爆与防火:印度三个十年的经验分析

获取原文
获取原文并翻译 | 示例
           

摘要

This paper reports the salient performance and the effect of the combination of influencing sensing logics on the protection of transformers against explosion and subsequent fire. It is an analysis of nearly three decades of field experience of over 12000 nitrogen gas based 'transformer explosion prevention & fire protection system' connected to the medium and high voltage power transformers in the range of 11kV to 765kV and in the power range of 750 KVA to bank of 1500 MVA. Though this experience covers worldwide, more emphasis is placed on the Indian installations. Over 100 successful operations of the protection systems have been so far reported covering low to medium to high fault energy levels and documented by the utilities. The paper is based on the field experience of the twin combo-sensing principles of most proven protection of transformer i.e. electrical differential relay protection combined with the rapid pressure sensing techniques as the most reliable sensing systems which serve as the backbone of an efficient explosion prevention system. Reference has been made to the reasons leading to the successful operation of the protection system which have been analysed and documented by various utilities. Some of the typical failures have been indicated in the paper. The principle of operation of the Nitrogen Gas based Transformer Explosion Prevention and Fire Protection System (referred hereinafter as the 'Protection System') is by now well-known and for that reason, is not described in the paper in detail.
机译:本文报告了显着的性能以及影响感测逻辑的组合对变压器防止爆炸和随后起火的影响。它分析了连接到11kV至765kV和750 KVA功率范围的中压和高压电力变压器的12000多种基于氮气的“变压器防爆和防火系统”,近三十年的现场经验到1500 MVA的银行。尽管这种经验涵盖了全世界,但更多的重点放在了印度装置上。迄今为止,据报道,该保护系统已成功运行了100多次,涵盖了从低到中到高的故障能级,并由公用事业部门记录在案。本文基于最成熟的变压器保护的双重组合传感原理的现场经验,即电气差动继电保护与快速压力传感技术相结合,是最可靠的传感系统,是高效防爆系统的基础。已经提到了导致保护系统成功运行的原因,已经由各种公用事业公司进行了分析和记录。本文已经指出了一些典型的故障。迄今为止,基于氮气的变压器防爆和防火系统(以下称为“保护系统”)的工作原理是众所周知的,因此在本文中不再详细描述。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号