Evaporation Heat Transfer and Pressure Drop of Refrigerant R-410A Flow in a Vertical Plate Heat Exchanger

机译:垂直板式热交换器中制冷剂R-410A的蒸发传热和压降

获取原文
获取原文并翻译 | 示例
           

摘要

Experiments are carried out here to measure the evaporation heat transfer coefficient h_r and associated frictional pressure drop ΔP_f in a vertical plate heat exchanger for refrigerant R-410A. The heat exchanger consists of two vertical counterflow channels which are formed by three plates whose surface corrugations have a sine shape and a chevron angle of 60 deg. Upflow boiling of refrigerant R-410A receives heat from the hot downflow of water. In the experiments, the mean vapor quality in the refrigerant channel is varied from 0.10 to 0.80, the mass flux from 50 to 100 kg/m~2s, and the imposed heat flux from 10 to 20 kW/m~2 for the system pressure fixed at 1.08 and 1.25 MPa. The measured data indicate that both h_r and ΔP_r increase with the refrigerant mass flux except at low vapor quality. In addition, raising the imposed heat flux is found to significantly improve h_r for the entire range of the mean vapor quality. However, the corresponding friction factor f_(tp) is insensitive to the imposed heat flux and refrigerant pressure. Based on the present data, empirical correlations are provided for h_r and f_(tp), for R-410A in the plate heat exchanger.
机译:在此进行实验以测量用于制冷剂R-410A的垂直板式热交换器中的蒸发传热系数h_r和相关的摩擦压降ΔP_f。热交换器由两个垂直的逆流通道组成,两个垂直的逆流通道由三块板组成,其表面波纹呈正弦形,人字形角度为60度。制冷剂R-410A的上流沸腾从水的热下行流中吸收热量。在实验中,制冷剂通道中的平均蒸汽质量在0.10到0.80之间变化,质量通量在50到100 kg / m〜2s之间变化,系统压力施加的热通量在10到20 kW / m〜2之间变化固定在1.08和1.25 MPa。测得的数据表明,h_r和ΔP_r随制冷剂质量通量的增加而增加,除了蒸汽质量较低时。此外,发现在整个平均蒸汽质量范围内提高施加的热通量可以显着提高h_r。但是,相应的摩擦系数f_(tp)对施加的热通量和制冷剂压力不敏感。基于当前数据,为板式热交换器中的R-410A提供了h_r和f_(tp)的经验相关性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号