摘要

Distribution systems operators are often confronted with declined power quality, which can cause substantial economical losses. The problem analyzed in paper concerns thyristor controlled direct current motor used for ski-lift in ski resort as a source of disturbances with negative impact on sensitive electric equipment, which is then unable to operate correctly. To solve mentioned problems, series of measurements of voltage quality parameters were carried out according to the respective valid standards. Crucial power quality parameters necessary for parallel power active filter design were then analyzed. Power active filter compensates power factor and filters characteristic current harmonics. After power active filter was put into operation, power quality problems were eliminated. Payback period is estimated up to four years.
机译:配电系统运营商经常面临着电能质量下降的问题,这可能会造成巨大的经济损失。论文中分析的问题涉及用于滑雪胜地的滑雪缆车的晶闸管控制直流电动机,它是对敏感电气设备造成负面影响的干扰源,因此无法正常运行。为了解决上述问题,根据各自有效的标准对电压质量参数进行了一系列测量。然后分析了并联电源有源滤波器设计所需的关键电源质量参数。功率有源滤波器可补偿功率因数并过滤特征电流谐波。电力有源滤波器投入运行后,电力质量问题得以消除。投资回收期估计为四年。