From Chip to Cooling Tower Data Center Modeling: Influence of Server Inlet Temperature and Temperature Rise Across Cabinet

机译:从芯片到冷却塔数据中心建模:服务器入口温度和整个机柜温度升高的影响

获取原文
获取原文并翻译 | 示例
           

摘要

To achieve reductions in the power consumption of the data center cooling infrastructure, the current strategy in data center design is to increase the inlet temperature to the rack, while the current strategy for energy-efficient system thermal design is to allow increased temperature rise across the rack. Either strategy, or a combination of both, intuitively provides enhancements in the coefficient of performance of the data center in terms of computing energy usage relative to cooling energy consumption. However, this strategy is currently more of an empirically based approach from practical experience, rather than a result of a good understanding of how the impact of varying temperatures and flow rates at rack level influences each component in the chain from the chip level to the cooling tower. The aim of this paper is to provide a model to represent the physics of this strategy by developing a modeling tool that represents the heat flow from the rack level to the cooling tower for an air cooled data center with chillers. This model presents the performance of a complete data center cooling system infrastructure. After detailing the model, two parametric studies are presented that illustrate the influence of increasing rack inlet air temperature, and temperature rise across the rack, on different components in the data center cooling architecture. By considering the total data center, and each component's influence on the greater infrastructure, it is possible to identify the components that contribute most to the resulting inefficiencies in the heat flow from chip to cooling tower and thereby identify the components in need of possible redesign. For the data center model considered here it is shown that the strategy of increasing temperature rise across the rack may be a better strategy than increasing inlet temperature to the rack.
机译:为了减少数据中心冷却基础设施的功耗,数据中心设计中的当前策略是提高机架的入口温度,而节能系统散热设计的当前策略是允许整个机架温度升高。架。无论是策略还是两者的组合,都可以在计算能耗方面相对于冷却能耗来直观地提高数据中心的性能系数。然而,该策略目前更多是基于实践经验的基于经验的方法,而不是对机架级温度和流速变化的影响如何影响从芯片级到冷却的链中每个组件的良好理解的结果塔。本文的目的是通过开发一种建模工具来提供一个表示这种策略的物理模型,该工具表示带有冷却器的空冷数据中心从机架级到冷却塔的热流。该模型展示了完整的数据中心冷却系统基础架构的性能。详细说明模型后,将进行两项参数研究,以说明机架入口空气温度升高和机架上温度升高对数据中心冷却架构中不同组件的影响。通过考虑整个数据中心以及每个组件对更大基础架构的影响,可以确定导致从芯片到冷却塔的热流效率低下最大的组件,从而确定需要重新设计的组件。对于此处考虑的数据中心模型,已显示出增加机架上温度升高的策略可能比增加机架的入口温度更好。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号