首页> 外文期刊>Journal of Civil Engineering and Management >NUMERICAL STUDIES ON SMOKE SPREAD IN THE CAVITY OF A DOUBLE-SKIN FACADE
【24h】

NUMERICAL STUDIES ON SMOKE SPREAD IN THE CAVITY OF A DOUBLE-SKIN FACADE

机译:双表皮腔中烟气扩散的数值研究

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

In this paper, influence of two key factors, fire room height and outer pane tilt angle, on smoke spread in the cavity of a double-skin facade (DSF) was studied numerically. The fire room was located adjacent to the DSF on the 2nd, 4th and 6th floors, respectively. The outer pane tilt angle varied at 80 degrees, 90 degrees and 100 degrees. All cases were under two fire heat release rates of 1 MW and 5 MW. Results suggested that fire room height and outer pane tilt angle had significant effects on smoke spread in the cavity. For different fire room heights, there were two markedly different scenarios of smoke spread in the cavity between two vertical panes in a high-rise building. For outer pane tilt angle, the DSF with an inward tilted or vertical outer pane was dangerous for the upper floors due to hot smoke adhering to the upper inner pane. However, the turbulent vortex in the DSF with an outward tilted outer pane prevented hot smoke flowing out from the fire room.
机译:本文研究了防火室高度和外窗格倾斜角这两个关键因素对双层幕墙(DSF)腔内烟气扩散的影响。消防室分别位于2楼,4楼和6楼的DSF附近。外窗格的倾斜角度在80度,90度和100度之间变化。所有案例均处于两种火热释放速率下:1 MW和5 MW。结果表明,防火室的高度和外窗格的倾斜角度对烟气在腔体内的扩散有显着影响。对于不同的防火室高度,高层建筑中两个垂直窗格之间的空腔中散布着两种明显不同的烟雾场景。对于外玻璃板的倾斜角度,由于热烟气附着在上部内玻璃板上,因此带有向内倾斜或垂直外玻璃板的DSF对上层地板是危险的。但是,DSF中的湍流涡旋带有向外​​倾斜的外窗格,阻止了热烟从防火室流出。