Live-Load Testing and Long-Term Monitoring of the Varina-Enon Bridge: Investigating Thermal Distress

机译:Varina-Enon桥的活载测试和长期监控:研究热应力

获取原文
获取原文并翻译 | 示例
           

摘要

During detailed visual inspections, inspectors on the Varina-Enon Bridge noticed a significant flexural crack opening, visually estimated at 1.5 mm under traffic, on the last span of the approach structure among other significant cracks on June 29, 2012. To investigate the causes of the observed cracking, live-load testing, long-term monitoring, and structural analysis were used including 77 total strain, crack displacement, deflection, and temperature sensors. The live-load test produced a crack opening of approximately 0.5 mm when under a less-severe thermal gradient. The collected data indicated the crack opening was greatly influenced by interaction of vehicular loads and thermal gradient magnitude. There were 389 crack openings larger than 0.0625 mm over the 17 months of the long-term monitoring, with a maximum measured crack opening of approximately 0.76 mm. Maximum measured thermal gradients were found to be in excess of the as-built design thermal gradient but similar to the current design thermal gradient. This may indicate potential underestimation of the maximum design thermal gradient, but would require a more robust study. (C) 2018 American Society of Civil Engineers.
机译:在进行详细的目视检查时,Varina-Enon桥的检查人员在2012年6月29日的进近结构的最后跨度中发现了一个大的挠曲裂缝开口,目视估计在行车中为1.5毫米。使用观察到的裂纹,活载测试,长期监测和结构分析,包括77个总应变,裂纹位移,挠度和温度传感器。当在不太严重的热梯度下时,活载测试产生约0.5 mm的裂纹开口。收集到的数据表明,裂纹的开启受车辆载荷和热梯度大小的相互作用影响很大。在长期监测的17个月中,有389个大于0.0625毫米的裂纹开口,最大测量的裂纹开口约为0.76毫米。发现最大测得的热梯度超过了建成设计的热梯度,但与当前的设计热梯度相似。这可能表明可能会低估最大设计热梯度,但需要进行更可靠的研究。 (C)2018美国土木工程师学会。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号