Development of a Field Test Method to Evaluate Gaseous Air Cleaner Performance in a Multizone Building

机译:开发用于评估多区域建筑物中气态空气净化器性能的现场测试方法

获取原文
获取原文并翻译 | 示例
           

摘要

The performance of gaseous air cleaners for commercial and residential buildings has typically been evaluated using test protocols developed for a controlled laboratory chamber or a test duct. It is currently unknown how laboratory measurements relate to the actual performance of an air cleaner installed in a real building. However, to date, there are no air cleaner field test protocols available, thereby limiting the existing field data. The National Institute of Standards and Technology (NIST) has conducted a series of experiments to support test procedure development for evaluating the installed performance of gaseous air cleaning equipment, as well as metrics for characterizing field performance. To date, over 100 experiments have been completed, of which 23 portable air cleaner experiments and 6 in-duct air cleaner experiments are described in this paper. Tests were conducted in a finished three-bedroom/two-bathroom manufactured house equipped with several gas chromato-graphs to semi-continuously measure air change rates and volatile organic compound concentrations. Experimental variables included air cleaner location, isolation of zones by closing doors, and contaminant source location. For each experiment, air cleaner removal of decane was directly measured using the air cleaner inlet and outlet concentrations, as well as with mass balance analyses using measured room concentrations. With a verified mass balance model, a field performance metric was developed to compare installed whole-building performance to the performance predicted by a laboratory result. The results provide insight into the protocols and metrics that might prove useful for characterizing the field performance of air cleaners as well as the impact of air cleaner removal on zonal concentration levels in a variety of situations.
机译:典型地,已经使用针对受控实验室室或测试管道开发的测试规程来评估用于商业和住宅建筑物的气态空气净化器的性能。目前尚不知道实验室测量值与安装在真实建筑物中的空气滤清器的实际性能之间的关系。但是,迄今为止,尚无可用的空气滤清器现场测试协议,从而限制了现有的现场数据。美国国家标准技术研究院(NIST)进行了一系列实验,以支持开发测试程序,以评估气态空气净化设备的安装性能以及表征现场性能的指标。迄今为止,已经完成了100多个实验,其中描述了23个便携式空气净化器实验和6个管道式空气净化器实验。测试在带有三张气相色谱图的成品三居室/两浴室成品房中进行,以半连续方式测量空气变化率和挥发性有机化合物的浓度。实验变量包括空气滤清器的位置,通过关闭门隔离区域以及污染源的位置。对于每个实验,使用空气滤清器的入口和出口浓度直接测量空气滤清器对癸烷的去除,并使用测得的室内浓度直接进行质量平衡分析。利用经过验证的质量平衡模型,开发了一种现场性能指标,用于将已安装的整栋建筑的性能与实验室结果预测的性能进行比较。结果提供了对协议和度量的深入了解,这些协议和度量可能被证明对于表征空气净化器的现场性能以及在各种情况下空气净化器的去除对区域浓度水平的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号