首页> 外文期刊>European Transactions on Electrical Power >Ground-Fault Fast Transients in Modern unit-Connected Generators
【24h】

Ground-Fault Fast Transients in Modern unit-Connected Generators

机译:现代单元发电机中的接地故障快速瞬变

获取原文
获取原文并翻译 | 示例

摘要

In this paper the ground-fault overvoltages in the circuits of unit-connected generators during interrupted arc- ing ground faults in the stator winding of the generator with the neutral grounded through the ground-fault neutraliser were analysed. Comparative simulation tests of ground-fault volatages and currents for units with the biggest difference in parameters at the neutralisation coefficient equal to 0.6 were carried out.
机译:本文分析了发电机定子绕组中电弧中断接地故障时,单元发电机的电路中的接地故障过电压,其中,中性点通过接地故障中和器接地。在中和系数等于0.6的情况下,对参数差异最大的单元进行了接地故障电压和电流的对比模拟测试。