Power Losses in a Three-Phase Single-Pole Gas-Insulated Transmission Line (GIL)

机译:三相单极气体绝缘传输线(GIL)的功率损耗

获取原文
获取原文并翻译 | 示例
       

摘要

This paper presents an analytical method for determining the power losses in the three-phase gas-insulated transmission line (i.e., high-current busduct) of circular cross-section geometry. The mathematical model takes into account the skin effect and the proximity effects, as well as the complete electromagnetic coupling between phase conductors and enclosures (i.e., screens). The power losses produced by high-current busducts are usually calculated numerically with the use of a computer. However, the analytical calculation of the power losses is preferable, because it results in a mathematical expression for showing its dependences on various parameters of the line arrangement. Moreover, knowledge of the relations between electrodynamics and constructional parameters is necessary in the optimization construction process of the high-current busducts.
机译:本文提出了一种用于确定圆形截面几何形状的三相气体绝缘输电线路(即大电流母线)中功率损耗的分析方法。数学模型考虑了趋肤效应和邻近效应,以及相导体和外壳(即屏幕)之间的完整电磁耦合。通常使用计算机以数字方式计算由大电流母线产生的功率损耗。然而,功率损耗的分析计算是优选的,因为它产生用于表示其对线路布置的各种参数的依赖性的数学表达式。此外,在大电流母线的优化构造过程中,必须了解电动力学和构造参数之间的关系。