首页> 外文期刊>International journal of thermal & environmental engineering >Smoke Clearance in an Underground Car Park using the Jet Fan System
【24h】

Smoke Clearance in an Underground Car Park using the Jet Fan System

机译:使用喷射风扇系统清除地下停车场的烟雾

获取原文
获取原文并翻译 | 示例

摘要

Fire propagation and control in underground car parks are of an important safety issue. This paper investigates the effect of the jet fan system on the smoke clearance in an underground car park using CFD simulations. Two fire locations were considered under a steady state fire source of 4 MW. The consideration of the fire zone was also studied. The underground car park used in this study is 5,290 m~2 in area with a height of 3.7 m. A comparison between CFD results and analytical correlations for the fire modeling was made. The ANSYS FLUENT 14.0 software was used for all simulations. The results showed that the temperature is limited to the zone, where the fire is detected, and it is within an accepted range. The CO_2 mass fraction was presented and showed how the jet fans contribute in reducing the smoke density and hence improve the visibility. It was found that dividing the car park into zones is highly recommended and should be taken in the design of the jet fan system.
机译:地下停车场的火灾蔓延和控制是一个重要的安全问题。本文利用CFD模拟技术研究了喷气式风扇系统对地下停车场烟雾清除的影响。在4兆瓦的稳态火源下考虑了两个火源。还研究了火区的考虑。本研究中使用的地下停车场面积为5290 m〜2,高度为3.7 m。比较了CFD结果和火灾模型的分析相关性。所有仿真均使用ANSYS FLUENT 14.0软件。结果表明,温度仅限于检测到火灾的区域,并且在可接受的范围内。介绍了CO_2的质量分数,并显示了射流风扇如何有助于降低烟气密度,从而提高可见度。已经发现,强烈建议将停车场划分为多个区域,并且应该在喷射风扇系统的设计中采用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号