This paper describes an experimental programme on vented hydrogen deflagrations, which formed part of the Hyindoor project, carried out for the EU Fuel Cells and Hydrogen Joint Undertaking. The purpose of this study was to investigate the validity of analytical models used to calculate overpressures following a low concentration hydrogen deflagration. Other aspects of safety were also investigated, such as lateral flame length resulting from explosion venting. The experimental programme included the investigation of vented hydrogen deflagrations from a 31 m(3) enclosure with a maximum internal overpressure target of 10 kPa (100 mbar). The explosion relief was provided by lightly covered openings in the roof or sidewalls. Uniform and stratified initial hydrogen distributions were included in the test matrix and the location of the ignition source was also varied. The maximum hydrogen concentration used within the enclosure was 14% v/v. The hydrogen concentration profile within the enclosure was measured, as were the internal and external pressures. Infrared video images were obtained of the gases vented during the deflagrations. Findings show that the analytical models were generally conservative for overpressure predictions. Flame lengths were found to be far less than suggested by some guidance. Along with the findings, the methodology, test conditions and corresponding results are presented. (C) 2016 Published by Elsevier Ltd on behalf of Hydrogen Energy Publications LLC.
机译:本文介绍了有关排放氢气爆燃的实验程序,该程序是Hyindoor项目的一部分,是针对EU燃料电池和氢气联合事业开展的。这项研究的目的是调查低浓度氢爆燃后用于计算超压的分析模型的有效性。还对安全性的其他方面进行了研究,例如由爆炸引起的侧向火焰长度。实验程序包括调查从31 m(3)外壳排出的氢爆燃,最大内部超压目标为10 kPa(100 mbar)。爆炸缓解是通过屋顶或侧壁上的浅覆盖开口提供的。测试矩阵中包括均匀且分层的初始氢分布,并且点火源的位置也有所变化。外壳内使用的最大氢浓度为14%v / v。测量外壳内的氢气浓度曲线,以及内部和外部压力。获得爆燃期间排出的气体的红外视频图像。研究结果表明,对于超压预测,分析模型通常较为保守。发现火焰长度远小于某些指导所建议的长度。连同发现,介绍了方法,测试条件和相应的结果。 (C)2016由Elsevier Ltd代表Hydrogen Energy Publications LLC发布。

著录项

  • 来源
    《International journal of hydrogen energy》 |2017年第11期|7565-7576|共12页
  • 作者单位

    Hlth & Safety Lab, Harpur Hill, Buxton SK17 9JN, England;

    Hlth & Safety Lab, Harpur Hill, Buxton SK17 9JN, England;

    Hlth & Safety Lab, Harpur Hill, Buxton SK17 9JN, England;

    Hlth & Safety Lab, Harpur Hill, Buxton SK17 9JN, England;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);美国《生物学医学文摘》(MEDLINE);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Experiment; Vented; Hydrogen; Explosion; Hyindoor; Analytical;