首页> 外文期刊>International Journal of Heat and Mass Transfer >Transient behavior of run-around heat and moisture exchanger system. Part I: Model formulation and verification
【24h】

Transient behavior of run-around heat and moisture exchanger system. Part I: Model formulation and verification

机译:四处循环的湿热交换系统的瞬态行为。第一部分:模型制定和验证

获取原文
获取原文并翻译 | 示例

摘要

In Part I, a numerical model for coupled heat and moisture transfer in a run-around heat and moisture exchanger with a liquid desiccant coupling fluid is developed. The numerical model is two dimensional, transient and is formulated using the finite difference method with an implicit time discretization. The results from the numerical model for the case of only heat transfer for a single heat exchanger are compared to an available analytical solution and good agreement is obtained. For the simultaneous heat and moisture transfer in the run-around membrane energy exchanger (RAMEE), a comparison between numerical model results and experimental measurements obtained from laboratory testing for both sensible and latent effectiveness showed satisfactory agreement at different operating conditions. Part II of this paper applies the model for a range of initial conditions [32].
机译:在第一部分中,建立了一种在液体和干燥剂耦合的情况下,在周转式热湿交换器中进行热湿耦合耦合的数值模型。数值模型是二维的,是瞬态的,是使用带有隐式时间离散化的有限差分法来建立的。将仅单个热交换器传热情况下的数值模型结果与可用的分析解决方案进行比较,并获得良好的一致性。对于在周向膜式能量交换器(RAMEE)中同时进行的热量和水分传递,数值模型结果与从实验室测试中获得的显着和潜在有效性的实验测量结果之间的比较表明,在不同的操作条件下具有令人满意的一致性。本文的第二部分将模型应用于一系列初始条件[32]。