Optimal placement and parameter setting of SVC and TCSC using PSO to mitigate small signal stability problem

机译:使用PSO优化SVC和TCSC的位置和参数设置以缓解小信号稳定性问题

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

This paper aims to select the optimal location and setting parameters of SVC (Static Var Compensator) and TCSC (Thyristor Controlled Series Compensator) controllers using PSO (Particle Swarm Optimization) to mitigate small signal oscillations in a multimachine power system. Though Power System Stabilizers (PSSs) associated with generators are mandatory requirements for damping of oscillations in the power system, its performance still gets affected by changes in network configurations, load variations, etc. Hence installations of FACTS devices have been suggested in this paper to achieve appreciable damping of system oscillations. However the performance of FACTS devices highly depends upon its parameters and suitable location in the power network. In this paper the PSO based technique is used to investigate this problem in order to improve the small signal stability. An attempt has also been made to compare the performance of the TCSC controller with SVC in mitigating the small signal stability problem. To show the validity of the proposed techniques, simulations are carried out in a multimachine system for two common contingencies, e.g., load increase and transmission line outage. The results of small signal stability analysis have been represented employing eigenvalue as well as time domain response. It has been observed that the TCSC controller is more effective than SVC even during higher loading in mitigating the small signal stability problem.
机译:本文旨在使用PSO(粒子群优化)选择SVC(静态无功补偿器)和TCSC(晶闸管控制的串联补偿器)控制器的最佳位置和设置参数,以减轻多机电源系统中的小信号振荡。尽管与发电机关联的电力系统稳定器(PSS)是阻尼电力系统振荡的强制性要求,但其性能仍然会受到网络配置变化,负载变化等的影响。因此,本文建议安装FACTS设备以:实现对系统振荡的明显衰减。但是,FACTS设备的性能在很大程度上取决于其参数和在电网中的合适位置。在本文中,基于PSO的技术用于研究此问题,以提高小信号的稳定性。还尝试将TCSC控制器与SVC的性能进行比较,以缓解小信号稳定性问题。为了显示所提出的技术的有效性,在多机器系统中针对两个常见的意外情况进行了仿真,例如负载增加和传输线路中断。小信号稳定性分析的结果已使用特征值和时域响应表示。已经观察到,即使在较高负载期间,TCSC控制器也比SVC更有效,以减轻小信号稳定性问题。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号