Heat transfer and pressure drop characteristics of forced convective evaporation in horizontal tubes with coiled wire inserts

机译:盘绕插入式水平管中强制对流蒸发的传热和压降特性

获取原文
获取原文并翻译 | 示例
           

摘要

Heat transfer enhancement and pressure drop increasing during evaporation of R-134a due to the presence of coiled wire insert inside a horizontal evaporator was studied experimentally. The test evaporator was an electrically heated copper tube of 1200 mm length and 7.5 mm inside diameter. Helically wire coils with different wire diameters of 0.5, 0.7, 1.0 and 1.5 mm and different coil pitches of 5, 8, 10 and 13 mm were made and used in full length of the test evaporator. For each inserted tube and also the plain tube, several test runs were carried out with different mass velocities and heat fluxes. From analysis of acquired data, it was found that the coiled wire inserts enhance the heat transfer coefficient but with a higher penalty due to the increasing of pressure drop, in comparison to that for the plain flow. An empirical correlation has been developed to predict the heat transfer coefficient during evaporation inside a horizontal tube in the presence of a coiled wire insert.
机译:实验研究了由于水平蒸发器内部存在盘绕的金属丝而导致的R-134a蒸发过程中的传热增强和压降增加。测试蒸发器是长度为1200 mm,内径为7.5 mm的电加热铜管。制成具有不同线径的0.5、0.7、1.0和1.5毫米,不同螺距的螺距为5、8、10和13毫米的螺旋线线圈,并将其用于测试蒸发器的全长。对于每个插入的管以及普通管,以不同的质量速度和热通量进行了几次测试。通过对获得的数据的分析,发现与普通流动相比,盘绕线插入物增强了传热系数,但是由于压降的增加而具有更高的损失。已经建立了经验相关性以预测在存在盘绕的金属丝插入物的情况下在水平管内蒸发期间的热传递系数。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号