首页> 外文期刊>IEEE Industry Applications Magazine >Arc-Flash Incident Energy Variations: A Study of Low-Voltage Motor Control Center Unit Configurations and Incident Energy Exposure
【24h】

Arc-Flash Incident Energy Variations: A Study of Low-Voltage Motor Control Center Unit Configurations and Incident Energy Exposure

机译:弧闪事件能量变化:低压电机控制中心单元配置和事件能量暴露的研究

获取原文
获取原文并翻译 | 示例
           

摘要

There has been significant progress in arc-flash research in recent years, but there has been little focus on how the internal configuration of equipment affects the released incident energy. The relationship between low-voltage motor control center (MCC) unit configurations and incident energy exposure resulting from an arc flash is examined in this article. Testing was conducted using actual MCC structures and units. The design of experiment (DOE) methodology was used to analyze several MCC configuration variables, including unit type, unit size, percent fill of unit, power wire size and length, location of the unit within the structure, and their relationships to incident energy as well as arcing duration and arcing current. The results from 24 arcing tests were analyzed, and the magnitude of incident energy measured during the events was observed to be related to the percent fill of components within the units and properties of interior unit surfaces.
机译:近年来,弧闪研究取得了重大进展,但很少关注设备的内部配置如何影响释放的入射能量。本文研究了低压电动机控制中心(MCC)单元配置与电弧闪光引起的入射能量暴露之间的关系。测试是使用实际的MCC结构和单元进行的。实验设计(DOE)方法用于分析多个MCC配置变量,包括单元类型,单元尺寸,单元填充百分比,电源线尺寸和长度,单元在结构中的位置以及它们与入射能量的关系。以及电弧持续时间和电弧电流。分析了来自24个电弧试验的结果,观察到在事件期间测得的入射能量的大小与单位内组件的填充百分比和内部单位表面的特性有关。

著录项

  • 来源
    《IEEE Industry Applications Magazine》 |2014年第3期|40-45|共6页
  • 作者

  • 作者单位
  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号